3-O&M_Settings_r1r Section 3Page 5
EBTRON, Inc • 1663 Hwy 701 S., Loris, SC 29569 • Toll Free: 800-2EBTRON (232-8766) • Fax: 843-756-1828 • EBTRON.com
Changing the transmitter from 1 to 2 locations, or vice versa, restores factory default settings.
Modifications made by the user are lost.
Dual location applications require that the probes are installed in the proper locations and properly
connected to the transmitter. See Section 1 for more information.
3.3. GENERAL SETTINGS
The GENERAL submenu contains the following parameters:
• NAME (Location Name)
• SERV (Service Description)
• AIRFLOW (Airflow Calculation Method)
• ALT (Altitude)
• INTG (Airflow Output Integration)
• LLIMIT (Low Limit Airflow Cutoff)
• AREA (Area at the Measurement Location)
• DPCONVERT (Differential Pressure Conversion) -B probe type only
• DIRECTION (Uni or Bidirectional Measurement) -B probe type only
• TEMPMETH (Temperature Averaging Method)
• H CONFIG (Relative Humidity Sensor Configuration) -P/H probe type only
• Pb CORR (Barometric Pressure Correction) -P/H probe type only
• EXT CAB (Extension Cable Length)
3.3.1. Location Name [NAME]
The alpha-numeric name of the location being served.
[Menu path: SETTINGS >↓ GENERAL > NAME]
Default: Transmitter serial number unless a valid location name is provided at the time of order.
Optional Settings: User defined in field using pushbutton interface (up to 16 characters can be entered).
Enter edit mode by pressing enter when *NAME={parameter name}↑↓ is shown. Use the ↑ and ↓
pushbuttons to select the alpha-numeric character for each character position in the NAME string.
Press the ENT pushbutton to move to the next character position to the right. Press the ESC
pushbutton to move to the previous character position to the left. Press and hold the ENT
pushbutton for 2 seconds to save the name. Press and hold the ESC pushbutton for 2 seconds to
exit without accepting changes. The first 8 digits of the name are displayed on the LCD as
*NAME={parameter name}↑↓.
Press the ENT pushbutton from the *NAME={parameter name}↑↓ and scroll through the name
parameter using the ENT pushbutton to view names longer than 8 characters. Press and hold the
ESC pushbutton to exit edit mode without making changes to the NAME parameter.
Use the service description to differentiate the location name of transmitters configured for dual
locations.