1. SECTION OVERVIEW
This section provides installation and wiring instructions for Advantage IV and EB-Flow2 remote transmitters.
1.1. SENSOR PROBES SUPPORTED
Transmitters in this manual support the following sensor probe types:
• -P duct/plenum probe
• -U universal mount probe
• -T terminal unit small duct probe
• -F fan inlet probe
• -B bleed sensor probe
1.2. SENSOR PROBE MOUNTING
1.2.1. Locating Probes
Sensor probe placement guidelines are located in the Appendix A – Placement Guidelines section at the end
of this document.
If minimum placement guidelines cannot be achieved, installed accuracy may be compromised.
Transmitters can be field adjusted to match a third-party measurement. Adjusted field measurements
typically result in comparative readings within ±3% of the third-party measurement. Be advised that
the third-party measurement may have uncertainties greater than or equal to ±10% and should only
be used to adjust the airflow measurement device if the probes do not meet minimum placement
requirements and the discrepancy is greater than the uncertainty of the third-party source.
1.2.2. Installation
Installation guides for each probe type are located in the Appendix B – Sensor Probe Installation Guides
section at the end of this document.
Sensor probes must be mounted and spaced properly to achieve the specified installed accuracy.
1.3. TRANSMITTER MOUNTING
Installation guides for each transmitter model are located in the Appendix C – Transmitter Installation Guides
section at the end of this document.
Mount transmitters in a location protected from moisture, rain and snow with an ambient temperature between
-20 and 120 °F [-28.9 to 48.9 °C]. Provide a weatherproof enclosure and mount away from direct sunlight
when outdoor mounting is required.
Transmitters have an LCD and four-button user interface. Select a mounting location where the LCD and
pushbutton interface are accessible during normal operation.