3-O&M_Settings_r1r Section 3Page 30
EBTRON, Inc • 1663 Hwy 701 S., Loris, SC 29569 • Toll Free: 800-2EBTRON (232-8766) • Fax: 843-756-1828 • EBTRON.com
3.7.7.2. MODBUS
Not applicable.
3.8. LON NETWORK SETTINGS
One Lonworks free topology connection is provided with the following transmitter models:
Advantage IV Product Line
o Models with the third digit of the model code equal to F or L
There are no transmitter settings for Lon.
3.9. RF-LINK SETTINGS
One proprietary wireless connection is provided with the following transmitter models:
Advantage IV Product Line
o Models with the third digit of the model code equal to W
The RF-Link submenu contains the following parameters:
RFLINK COM (Enable and Pair Wireless Connection)
3.9.1. Enable and Pair Wireless Communications [RFLINK COM]
Use the following procedure if a RF-Link wireless connection is used to communicate with an EBTRON
Commissioner or other RF-Link compatible EBTRON master transceiver:
Step 1 Make sure the master transceiver is ON and in the ADD DEVICE mode.
Step 2 Set the RFLINK COM parameter to ON to initiate pairing.
[Menu path: SETTINGS >↓ RF-LINK > RFLINK COM]
Setting RFLINK COM to ON will initiate pairing between the transmitter and the EBTRON master
transceiver. The transmitter will display "CONNECTING" during pairing. When the connection is
made "CONNECTED" will be displayed. If the connection fails "CON FAILED" will be displayed.
Press ENT or ESC after pairing to return to submenu prompt for RFLINK COM. If the connection was
successful, *RFLINK COM=ON will be displayed.
Do not have multiple master transceivers in the ADD DEVICE mode at the same time.
3.10. USB SETTINGS
One USB port for connection to a Type A USB memory device “thumb drive” (by others) is provided on the
following models:
Advantage IV Product Line
o Models with the third digit of the model code equal to D or U
Transmitters with a USB data logger log the average airflow, average temperature, individual sensor
node airflow and the individual sensor node temperature at 5-minute intervals using Universal Time
Coordinated (UTC) based on an onboard real-time clock, whenever power is applied to the
transmitter. Data files are automatically appended on power-up. The time zone and interval can be
modified by the user using EB-Link software.