3-O&M_Settings_r1r Section 3Page 27
EBTRON, Inc • 1663 Hwy 701 S., Loris, SC 29569 • Toll Free: 800-2EBTRON (232-8766) • Fax: 843-756-1828 • EBTRON.com
3.6.3.2. MODBUS
Default: 19200 (bps)
Optional Settings: 76800, 38400, 9600
3.6.4. Parity [PARITY]
3.6.4.1. BACNET
Not applicable.
3.6.4.2. MODBUS
Sets the parity bit for network data checking.
[Menu path: SETTINGS >↓ RS485 >↓ PARITY]
Default: EVEN
Optional Settings: ODD, NONE1 (one stop bit), NONE2 (two stop bits)
3.6.5. Device Instance Number [NETDI]
3.6.5.1. BACNET
Sets the device instance number of the transmitter.
[Menu path: SETTINGS >↓ RS485 >↓ NETDI]
Default: 2
Optional Settings: 0 to 4194302
3.6.5.2. MODBUS
Not applicable.
3.6.6. Enable RS-485 Communications [RS485 COM]
Enable the transmitter for RS-485 network communications.
[Menu path: SETTINGS >↓ RS485 >↓ RS485 COM]
Default: OFF
Optional Settings: ON
Do not enable transmitter network communications until the transmitter network settings are properly
configured to avoid addressing conflicts.
3.7. ETHERNET NETWORK SETTINGS
One Ethernet network connection is provided with the following transmitter models:
Advantage IV Product Line
o Models with the third digit of the model code equal to B, E or M

Questions and Answers: