3-O&M_Settings_r1r Section 3Page 17
EBTRON, Inc • 1663 Hwy 701 S., Loris, SC 29569 • Toll Free: 800-2EBTRON (232-8766) • Fax: 843-756-1828 • EBTRON.com
The ANALOG OUTPUT submenu contains the following parameters:
AOUT (Analog Output Signal Type and Range)
ON FAIL (Analog Output on Total Sensor Failure)
AO1 ASGN (AO1 Assignment)
AO1 UM (AO1 Unit of Measure)
AO1 MS (AO1 Minimum Scale)
AO1 FS (AO1 Full Scale)
AO2 ASGN (AO2 Assignment)
The following parameters are only available when AO2 ASGN is equal to TEMP, AF2, F1-2 or F2-1
AO2 UM (AO2 Unit of Measure)
AO2 MS (AO2 Minimum Scale)
AO2 FS (AO2 Full Scale)
The following parameter is only available when AO2 ASGN is equal to ALRM, FA or TRBL
NO FAULT (AO2 Output on Inactive Notification Alarm)
The following parameters are only available with Advantage IV GTx116e remote transmitters that have the
humidity sensor option, /H, provided with the -P sensor probe type.
AO3 ASGN (AO3 Assignment)
AO3 UM (AO3 Unit of Measure)
AO3 MS (AO3 Minimum Scale)
AO3 FS (AO3 Full Scale)
3.5.1. Analog Output Signals [AOUT]
The analog output type and range for each of the analog outputs.
[Menu path: SETTINGS >↓ ANALOG OUT > AOUT]
3.5.1.1. ADVANTAGE IV MODELS
Default: 4-20mA (current)
Optional Settings: 0-5V, 0-10V (voltage)
Current output is “4-wire” type. Do not connect to a loop powered input that provides an excitation
voltage.
The output signal type of Advantage IV GTx108 and GTx116 transmitters (x=C and M) is selected
using switches SW1 and SW2 on the output card installed on the main circuit board for analog
outputs 1 and 2, respectively. The switch position must be in the VDC position for the optional 0-5V
or 0-10V signals to be available. Parameters for AOUT1 and AOUT2 will be displayed in lieu of
AOUT.
Output jumpers, OUT1 (AO1) and OUT2 (AO2) must be configured for the proper output
configuration, mA or VDC on Hybrid HTA104/HTA202 transmitters.
Output signals are isolated from the power supply.