3.15.6.2. ALL PROBE TYPES EXCEPT THE -B PROBE TYPE CONFIGURED FOR PRESSURE
(DPCONVERT=YES)
3.15.6.2.1. F_ADJ_UM = FPM [m/s]
Default: 0
Optional Settings: -99999 to 99999 (FPM) [-99.99 to 99.99 (m/s)]
3.15.6.2.2. F_ADJ UM = CFM [L/s]
Default: 0
Optional Settings: -99999 to 99999 (CFM [L/s])
3.15.6.3. -B PROBE TYPE CONFIGURED FOR PRESSURE (DPCONVERT=YES)
Default: 0
Optional Setting: -5.000 to 5.000 (iWG) [-1250 to 1250 (Pa)]
3.15.7. Temperature Adjustment
Refer to Section 4 if temperature adjustments are required.
The temperature output of the EBTRON device is velocity-weighted and more accurate than the
simple arithmetic average obtained by a field temperature measurement or traverse. A field
temperature measurement will not match the velocity-weighted output shown on the display. The
arithmetic average of the sensor nodes can be viewed through the DIAGNOSTICS Menu.
Making an adjustment to the temperature overrides EBTRON’s NIST traceable temperature
calibration.
Note: Section 3.15.8. only applies to Advantage IV GTx116e remote transmitters that have the
humidity sensor option, /H, provided with the -P sensor probe type.
3.15.8. Relative Humidity Adjustment
Refer to Section 4 if relative humidity adjustments are required.
The relative humidity output of the EBTRON device is velocity-weighted and more accurate than the
simple arithmetic average obtained by a field relative humidity measurement or traverse. A field
relative humidity measurement will not match the velocity-weighted output shown on the display. The
arithmetic average of the relative humidity sensor(s) can be viewed through the DIAGNOSTICS
Menu.