Do you have pressure in the
High and Low pressure
gauges?
Do a recovery or emptying phase.
Tubes or connections not
tight
-Check that the service hoses and
quick couplings are tight
-Do a vacuum phase of at least 5
minutes and check the tightness of
0.99 bar
Make a short filling of 100 g in the
service pipes and then a recovery,
then repeat the 5-minute vacuum test
on the service pipes.
ERROR
REFRIGERANT
PRESENCE IN THE A/C
SYSTEM