EasyManua.ls Logo

EET PMC-D726M - Display Screen Types; LCD Data Screens; LED Data Screens

Default Icon
54 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
CET Electric Technology
23
3.3 LED Pulse Outputs
The PMC-D726M comes standard with two LED Pulse Outputs on its front panel, labeled kWh and kvarh,
which can be used for kWh and kvarh energy pulsing if the EN PULSE is enabled (see Section 4.1.3
Energy Pulse Outputs for more information).
3.4 Display Screen Types
The front panel provides two display modes: Data Display and Setup Configuration. There are four
buttons on the front panel: <System>, <Phase>, <Energy> and <Setup>. The <Setup> button is only
used when configuring the meter. The <System>, <Phase> and <Energy> buttons are used in the Data
Display mode to view data on the front panel.
The following sections illustrate the display screens for the PMC-D726M model.
3.4.1 LCD Data Screens
Press button
Display screens
First row
Second row
Third row
<System>
Display 1 (default)
kW Total
I average
Total P.F.
Display 2
Frequency
ULN
1
average
ULL average
Display 3
Total kW
Total kvar
Total kVA
Display 4~
Inc (Calculated Neutral Current)
Display 5*
kW Tot Demand
kvar Tot Demand
kVA Tot Demand
Display 6
#
Voltage Unbalance
Display 7
#
Current Unbalance
<Phase>
Display 1
Ia
Ib
Ic
Display 2
1
Uan
Ubn
Ucn
Display 3
Uab
Ubc
Uca
Display 4
1
kWa
kWb
kWc
Display 5
1
kvara
kvarb
kvarc
Display 6
1
kVAa
kVAb
kVAc
Display 7
1
P.F.a
P.F.b
P.F.c
Display 8*
Ia Demand
Ib Demand
Ic Demand
Display 9
# 2
Uan /Uab THD
Ubn /Ubc THD
Ucn /Uca THD
Display 10
#
Ia THD
Ib THD
Ic THD
<Energy>
Display 1
kWh Import
Display 2
kWh Export
Display 3
kvarh Import
Display 4
kvarh Export
Display 5
kVAh
Display 6~9
#
kWh Import of T1 to T4
Display 10~13
#
kWh Export of T1 to T4
Display 14~17
#
kvarh Import of T1 to T4
Display 18~21
#
kvarh Export of T1 to T4
* Available in Firmware V1.01.03 or later.
#
Available in Firmware V1.01.04 or later
~ Available in Firmware V1.01.07 or later.
Table 3-4 PMC-D726M Data Display Screens
Notes:
1) This screen only appears when the Wiring Mode is set to Wye.
2) When the Wiring Mode is Delta, the phase A/B/C Voltage THD mean phase AB/BC/CA Voltage THD.
3.4.2 LED Data Screens
Press button
Display screens
First row
Second row
Third row
<System>
Display 1 (default)
I average
ULN
1
average
ULL average
Display 2
kW Total
kvar Total
kVA Total

Table of Contents

Related product manuals