3.5.3 Configuration
The Setup Configuration mode provides access to the following setup parameters:
Label
Parameters
Description
Range
Default
Menu
Main
Sub
PROG
Programming
Setup Configuration
Mode
/
/
PASS
Password
Enter Password
0 to 9999
ā€œ0ā€
PASS SET
Enter Sub Menu to
change password?
YES/NO
NO
NEW PASS
New Password
Change Password
0000 to 9999
ā€œ0ā€
SYS SET
Enter sub menu to set
system parameters?
YES/NO
NO
TYPE
Wiring Mode
Wiring connection
WYE/DELTA/DEMO
WYE
CT1
#
CT Primary
Current
1,2
CT Primary Current
1 to 30,000 (A)
5A
CT2
#
CT Secondary
Current
1,2
CT Secondary Current
1 to 5 (A)
5A
PT1
#
PT Primary
Voltage
1,3
PT Primary Voltage
1 to 1,000,000 (V)
100V
PT2
#
PT Secondary
Voltage
1,3
PT Secondary Voltage
1 to 690 (V)
100V
PF
P.F.
Convention
4
P.F. Convention
IEC/IEEE/-IEEE
IEC
KVA
kVA
Calculation
5
kVA Calculation Method
V/S
(V=Vector, S=Scalar)
V
CT A REV
Reverse CT A
Reverse Ia CT Polarity
YES/NO
NO
CT B REV
Reverse CT B
Reverse Ib CT Polarity
YES/NO
NO
CT C REV
Reverse CT C
Reverse Ic CT Polarity
YES/NO
NO
BLTO
Backlit Time-
Out
Set Backlight Time-out
0 to 60 min
3
COM SET
6
Enter sub menu to set
Comm. parameters?
YES/NO
NO
ID
Meter Address
Meter Address
1-247
100
BAUD
Baud rate
Data rate in bits per
second
1200/2400/4800/
9600/19200/38400
bps
9600
CFG
Comm. Port
Configuration
Data Format
8N2/8O1/8E1/8N1/
8O2/ 8E2
8E1
DMD SET~
Set Demand
parameters
Enter sub menu to set
demand parameters?
YES/NO
NO
PRD~
Sliding Window
Interval
Sliding window Interval
1 to 60 (min)
15
NMD~
Number of
Sliding
Windows
Number of Sliding
Windows
1 to 15
1
DMD CLR~
Clear All
Demand
Clear Present Demand,
Peak Demand Log of
This Month (Since Last
Reset) and Last Month
(Before Last Reset)
YES/NO
NO
AO SET
7
Enter sub menu to set
AO parameters
YES/NO
NO
AO TYPE
Analog Output
Type
Select between 0-20mA
or 4-20mA output
0-20/4-20
4~20
AO KEY
Analog Output
Parameter
The parameter to which
the Analog Output is
proportional
0-13 (See Table 3-7
for AO Key)
0
AO 0
AO Zero Scale
The parameter value
that corresponds to the
minimum Analog
Output of 0 mA or 4 mA
-999,999 to 999,999
0
AO 1
AO Full Scale
The parameter value
that corresponds to the
maximum Analog
-999,999 to 999,999
0