CET Electric Technology
27
Output of 20 mA
DO SET
8
Set DOs Control
DO1
DO1 Control
DO1 Control
ON/OFF/NRM
NRM
DO2
*
DO2 Control
DO2 Control
NRM
ENGY SET
Preset Energy
Values
Enter sub menu to
preset Energy Values
YES/NO
NO
kWh
kWh Import
Preset kWh Import
Value
0 to 99,999,999.9
0
kWh
kWh Export
Preset kWh Export
Value
0 to 99,999,999.9
0
kvarh
kvarh Import
Preset kvarh Import
Value
0 to 99,999,999.9
0
kvarh
kvarh Export
Preset kvarh Export
Value
0 to 99,999,999.9
0
kVAh
kVAh
Preset kVAh Value
0 to 99,999,999.9
0
ENGY PULS
Energy Pulsing
Enable kWh and kvarh
Energy Pulsing
YES/NO
YES
ENGY CNST
9
Pulse Constant
Pulse Constant
40
#
/100/400/1000
/3200/5000/6400
/12800
40/3200
ENGY CLR
Clear Energy
Clear all Energy
Registers
YES/NO
NO
SOE CLR
Clear SOE
Clear SOE Log
YES/NO
NO
TM SET
Set date and
time
Enter sub menu to set
date and time?
YES/NO
NO
DATE
Date
Enter the Current Date
YYYY-MM-DD
/
CLK
Clock
Enter the Current Time
HH:MM:SS
/
INFO
Information
(Read Only)
Check Meter
Information
YES/NO
NO
AMP SCAL
Current Input
Current Configuration
5A
10
/1A/40mA
#
5A
VOLT SCAL
Voltage Input
Voltage Configuration
415V
415V
FW
Firmware
Version
Firmware Version
e.g. 1.00.00 means
V1.00.00
/
PROT VER
Protocol
Version
Protocol Version
e.g. 2.1 means V2.1
/
UPDT
Update Date
Firmware Update Date
e.g. 20160603
/
*
Available in Firmware Version V1.00.03 (LED)/V1.01.03 (LCD) or later.
~Available in Firmware Version V1.00.04 (LED)/V1.01.04 (LCD) or later.
#
Available in Firmware Version V1.00.07 (LED)/V1.01.07 (LCD) or later.
Table 3-6 Setup Parameters
Notes:
1) PT Ratio and CT Ratio have been replaced by PT Primary, PT Secondary, CT Primary and CT Secondary since
Firmware Version V1.00.03 (LED)/V1.01.03 (LCD).
2) When the Current Input is 2.5mA (SCCTA Option for 5A SCCT), the CT Primary Current and CT Secondary
Current should be programmed to match the external CT's Primary and Secondary ratings, respectively.
When the Current Input is 40mA (SCCT Option for 100A-800A SCCT), the CT Primary Current should be
programmed as the selected SCCTs Nominal Current while the CT Secondary Current must be configured as
1.
3) PT Primary Voltage/PT Secondary Voltage must be no more than 10000. PT Ratio × CT Ratio x Rated Line
Voltage x Rated Current must be less than 790,000,000.
4) Power Factor Convention