EasyManua.ls Logo

EET PMC-D726M - Page 41

Default Icon
54 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
CET Electric Technology
41
described in Table 5-12.
Register
Property
Description
Format
10000-10007
RO
Event 1
See
Table 5-12 SOE
LOG Data
Structure
10008-10015
RO
Event 2
10016-10023
RO
Event 3
10024-10031
RO
Event 4
10032-10039
RO
Event 5
10040-10047
RO
Event 6
10048-10055
RO
Event 7
10056-10063
RO
Event 8
10064-10071
RO
Event 9
10072-10079
RO
Event 10
10080-10087
RO
Event 11
10088-10095
RO
Event 12
10096-10103
RO
Event 13
10104-10111
RO
Event 14
10112-10119
RO
Event 15
10120-10127
RO
Event 16
Table 5-11 SOE Log
Notes:
1) SOE LOG Data Structure
Offset
Property
Description
+0
RO
Storage location (0-15) in SOE buffer
+1 (Hi)
RO
Class (0-3)
+1 (Lo)
Event Classification (See Table 5-13)
+2 (Hi)
RO
High-order Byte: Year-2000
+2 (Lo)
Low-order Byte: Month
+3 (Hi)
RO
High-order Byte: Day
+3 (Lo)
Low-order Byte: Hour
+4 (Hi)
RO
High-order Byte: Minute
+4 (Lo)
Low-order Byte: Second
+5
RO
Millisecond
+6
RO
Event Value High-order Word
+7
RO
Event Value Low-order Word
Table 5-12 SOE LOG Data Structure
2) SOE Event Classification
Event
Classification
Sub-
Classification
Status
Event
Value
Description
0=
Operations
1
1 / 0
1/0
DI1 Inactive / DI1 Active
2
1 / 0
1/0
DI2 Inactive / DI2 Active
3
1 / 0
1/0
DO1 Inactive / DO1 Active
4
1 / 0
1/0
DO2 Inactive / DO2 Active
11
None
0
Clear all Energy Registers via the Front Panel
12
None
0
Clear all Energy Registers via the
Communications
13
None
0
Clear Present Demand, Peak Demand Log of
This Month (Since Last Reset) and Last Month
(Before Last Reset) via the Front Panel
14
None
0
Clear Peak Demand Log of This Month (Since
Last Reset) and Last Month (Before Last Reset)
via the Front Panel
15
None
0
Clear Present Demand, Peak Demand Log of
This Month (Since Last Reset) and Last Month
(Before Last Reset) through Communications
21
None
0
Clear SOE via Front Panel or through the
Communications
22
None
0
Power Off
31
None
0
Setup Parameter Changes via Front Panel
32
None
0
Setup Parameter Changes via Communication
3=Setpoint
1
None
Trigger
Value
Over Uln Setpoint Active
2
None
Over Ull Setpoint Active
3
None
Over Current Setpoint Active