CET Electric Technology
43
(Default = 100V)
6002
#
RW
PT Secondary Voltage
#1
INT32
1V to 690V
(Default = 100V)
6004
#
RW
CT Primary Current
#2
INT32
1A to 30,000A
(Default = 5A)
6006
#
RW
CT Secondary Current
#2
INT32
1A to 5A*
6008-6010
RW
Reserved
6011
RW
Wiring Mode
INT16
0=WYE*, 1=DELTA, 2=DEMO
6012
RW
Reserved
6013
RW
Unit ID
INT16
1 to 247
(Default = 100)
6014
RW
Baud rate
INT16
0=1200, 1=2400, 2=4800
3=9600*, 4=19200, 5=38400
6015
RW
Comm. Config.
INT16
0=8N2, 1=8O1, 2=8E1*
3=8N1, 4=8O2, 5=8E2
6016
RW
AO Key
3
INT16
0* (Ia)
6017
RW
AO Zero Scale
INT32
-999,999 to 999,999
6019
RW
AO Full Scale
INT32
-999,999 to 999,999
6021
RW
AO Type
INT16
0=4-20mA*, 1=0-20mA
6022
RW
Phase A CT
INT16
0=Normal*, 1=Reversed
6023
RW
Phase B CT
INT16
0=Normal*, 1=Reversed
6024
RW
Phase C CT
INT16
0=Normal*, 1=Reversed
6025
RW
PF Convention
INT16
0=IEC*, 1=IEEE, 2=-IEEE
6026
RW
kVA Calculation
INT16
0=Vector*, 1 =Scalar
6027
RW
Energy Pulse
INT16
0=Disable, 1=Enable*
6028
RW
Energy Pulse Constant
4
INT16
0=1000, 1=3200*
2=5000, 3=6400
4=12800, 5=100
6=400, 7=40
^
6029
RW
ARM before EXECUTE
for DO remote control
INT16
0=Disabled, 1=Enabled*
6030
RW
Clear SOE
5
INT16
Writing “0xFF00 to the
register clears SOE
6031
RW
Clear All Energy
Registers
INT16
Writing “0xFF00” to the
register to execute the
described action..
6032
RW
Clear Peak Demand of
This Month (Since Last
Reset)
~
and Last Month
(Before Last Reset)
UINT16
Writing “0xFF00” to the
register to execute the
described action.
6033
RW
Clear All Demand
6
~
UINT16
6034
RW
Demand Period
~
UINT16
1 to 60 (minutes), 15*
6035
RW
Number of Sliding
Windows
~
UINT16
1 to 15, 1*
6036
RW
Self-Read Time
7
UINT16
Default=0xFFFF
(Manual Reset)
*Default.
#
Available in Firmware V1.00.03 (LED)/V1.01.03 (LCD) or later.
~Available in Firmware V1.00.04 (LED)/V1.01.04 (LCD) or later.
^
Available in Firmware V1.00.07 (LED)/V1.01.07 (LCD) or later.
Table5-14 Setup Parameters
Notes:
1) PT Primary Voltage/PT Secondary Voltage must be no more than 10000. PT Ratio × CT Ratio x Rated Line
Voltage x Rated Current must be less than 790,000,000.
2) When the Current Input is 2.5mA (SCCTA Option for 5A SCCT), the CT Primary Current and CT Secondary
Current should be programmed to match the external CT's Primary and Secondary ratings, respectively.
When the Current Input is 40mA (SCCT Option for 100A-800A SCCT), the CT Primary Current should be
programmed as the selected SCCTs Nominal Current while the CT Secondary Current must be configured as
1.
3) AO Key
Value
Parameters
Value
Parameters
Value
Parameters
0
Ia
5
Ubc
10
kWc
1
Ib
6
Uca
11
kW Total
2
Ic
7
ULL avg
12
PF Total