ECH 200 BD
12/76
4.4.3 Alarm
ALL - 12-24 V~ output for alarm, maximum current 500 mA.
For models Ech 2xx BD the following parameters are available:
Pa H56 = determines the polarity of the alarm output:
0 = output is active (closed contact) when an alarm is active and when the machine is switched off.
1 = in the same conditions, the contact is open
Pa H57 = determines if the alarm is on with the machine on off from keyboard, with remote off and on stand-by
0 = alarm output not enabled in OFF or standby
1 = alarm output enabled in OFF or standby
The power supply to the alarm output must be kept separate from the controller power supply.
4.4.4 Fan module pilot output
TC - low voltage output piloting external fan control modules.
4.4.5 Optional output
EXPoptional internal output with configurable output.
For model Ech 210 BD the optional output is digital type and is open collector for piloting the second compressor’s relay:
Rear view: rear view of the control module
External relay: external relay
For model Ech 215 BD the optional output is ANALOGUE type and can be used for piloting 4-20mA or 0-10V fans (through
parameter Pa H25)
Rear view: rear view of the control module
Parameter Pa H25 must be configured to suit the version used, as shown
in the table below:
Value
Pa. Description
0 1 2
Pa H25 Optional output
configuration
parameter
Open Collector output for
compressor 2
Proportional condensation
fan control, 4-20 mA
Proportional condensation
fan control, 0-10 V
The analogue output value is directly proportionate to the external fan control.
For example: if the external fan control has an output of 50%,
with Pa H25= 1, the 4...20 mA output will have a value of 12 mA (50% calculated on the range 4…20), while the 0-10
V output will not be significant.
with Pa H25= 2, the 0-10 V output will have a value of 5 V (50% calculated on the range 0…10), while the 4...20 mA
output
will not be significant.
4.4.6 Remote keyboard output
KEYB - The keyboard output may be used for a remote keyboard.
Connect as shown in the diagram below:
Open collector
output
4-20 mA or 0-10 V
output
Optional output:
configuration
table
SERIAL KEYB
EXP
CONN A
CONN B
REAR VIEW
EXTERNAL RELAY
SERIAL KEYB
EXP
CONN A
CONN B
REAR VIEW
4-20 mA
GND
0-10 V