ECH 200 BD
25/76
Pa r03 Heating mode configuration off during heating On during heating (depending
on anti-freeze electrical heater
control)
Pa r04 Configuration of electrical heater control
probe in heating mode
controlled on the basis of AI1
(refer to connection diagrams)
if Pa H05 (config. AI1)= 1
otherwise off
Controlled on the basis of AI2
(refer to connection diagrams)
if Pa H06 (config. AI2)= 1
otherwise off
Pa r05 Configuration of control probe in cooling
mode
controlled on the basis of AI1
(refer to connection diagrams)
if Pa H05 (config. AI1)= 1
otherwise off
Controlled on the basis of AI2
(refer to connection diagrams)
if Pa H06 (config. AI2)= 1
Otherwise off
Pa r06 Configuration when OFF or on stand-by Off when instrument is OFF or
on stand-by
On when instrument is OFF or
on stand-by
6.5.1 Supplementary electrical heaters
If Pa r15 =1 electrical heaters become anti-freeze/supplementary electrical heaters.
Their operating mode is described in the paragraph on the supplementary electrical heater control
6.6 External anti-freeze electrical heaters
External anti-freeze electrical heaters are used on water-water machines with gas reversal.
They are connected to the triac TK output (refer to connection diagram) and controlled on the basis of probe AI3 (refer
to analogue inputs) .
They are active only if:
output TK is configured for anti-freeze electrical heaters, on a water-water machine with gas reversal (Pa F01=
2)
AI3 is configured as an NTC anti-freeze input on a water-water machine with gas reversal (Pa H07= 4)
6.7 Boiler
The output for boiler controller is relay NO4 (refer to connection diagram) with a suitable configuration.
The boiler output may operate in two different ways:
to supplement another heating resource
to provide heating with boiler only.
SUPPLEMENTARY BOILER:
The output is active if:
relay 4 configuration parameter, Pa H24= 2.
heat pump is declared present, Pa H28= 1.
AI4 is configured as an outdoor probe, Pa H08= 3.
HEATING BOILER:
The output is active if:
relay 4 configuration parameter, Pa H24= 2.
heat pump is declared not present (H28= 0)
The boiler is turned off if:
the device is operating in cooling mode
the device is on stand-by or OFF
there is a boiler shutdown alarm (refer to table of alarms)

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Eliwell ECH 200BD "Adaptive" and is the answer not in the manual?

Eliwell ECH 200BD "Adaptive" Specifications

General IconGeneral
BrandEliwell
ModelECH 200BD "Adaptive"
CategoryController
LanguageEnglish

Related product manuals