(((ELKRON))) - MP110
TECHNICAL CHARACTERISTICS OF EP100 PARALLEL INPUT EXPANSION MODULE
- Rated power supply voltage 10V5 to 15V -
- Absorption at 12V rated voltage Max 30mA with all inputs Not Connected
Max 26mA with all inputs balanced
- Type of communication Elkron serial protocol
- Max length of serial line from unit 500 meters* (2x0.75 cable sect for
feeder + 2 x 0.22 x data)
- Max number of expansions connectable
to MP110 system 4 (for 8 inputs each + 1 for 24h + 1 for aux. zone)
TECHNICAL CHARACTERISTICS OF ES100 INPUT SERIAL EXPANSION MODULE
- Operation in sole combination with the UR1Z serializer modules.
- Rated power supply voltage 10V5 to 15V -
- Absorption at 12V rated voltage Max 30mA with 8 UR1Z modules connected
- Type of communication Elkron serial protocol
- Max length of serial line from unit 500 meters* (2x0.75 cable sect. for
feeder + 2 x 0.22 x data)
- Max number of expansions connectable to the MP110 system 4 (for 8 URIZ modules each +
1 for 24h + 1 for aux. zone)
TECHNICAL CHARACTERISTICS OF DK2000M CONNECTOR LINKED TO MP110 SYSTEM
- Rated power supply voltage 12V- (drawn from motherboard-serial line)
- Absorption at 12V rated voltage 18mA (all zones OFF)
Max 30 mA(all zones ON + red led lit)
- Type of communication Elkron serial protocol
- Max length of serial line from unit 500 meters* (2x0.75 cable sect.
for feeder+ 2 x 0.22 x data)
- Max number of connectors connectable
to MP110 system 4
- Max number of programmable DK20 keys Unlimited
- Max number of random codes programmable
by the unit > 4 billion
* The maximum distance that can be reached is closely linked to the power supply cable section (+ and –), to the serial
line itself, and to absorption at the other end. In this connection,keep in mind that every 200m of cable with 2x0.75
mm² section, with 100mA absorption, determines a voltage drop of about 1V.
67