Section 2: Quick Start
Quick Start
2.2 Network Setup
This is only applicable if the Controlinc Auxiliary Control Module (ACM) and the
Communication Adapter Module (CAM) are installed and enabled. These instructions
assume all parameters have been set with the exception of the network node address.
1. Remain in the “SETUP” mode.
2. Select NEXT to advance through the displays until “NETWORK SETUP?” appears.
3. Rotate the control knob to YES. “NETWORK NODE ADDRESS XXX” appears.
4. Rotate the control knob to NO to increment the address numbers. Hold in the NO
position until the desired address is reached.
NOTE:
If the desired address is a lower number than what is displayed, continue to
increment the numbers until the highest numbered address is reached.
The address numbers will then start with the lowest numbered address
and continue to increment.
5. When the correct address is displayed, rotate the control knob to YES.
2.3 Check Settings
1. Operate the valve to the fully close position.
2. Verify the green LED is ON (default setting) and 0% is displayed.
3. Operate the valve to the fully open position.
4. Verify the red LED is ON (default setting) and 100% is displayed.