Installation and Operation Manual
E2K-405-0218 Rev. 2
February 2018
49
Section 5: Customizing Actuator Settings
Customizing Actuator Settings
Figure 5-6 Valve Control Setup
Associated choices are listed below each setting.
NO NO NO NO NO NO
Figure 5-6 Valve Control Setup
Go to Next Display
See Figure 5-4
YES YES
YES
Control Mode
<control mode>
YES
Position Bandwidth
=<x.x>%
YES
Speed Bandwidth
=<x.x>%
YES YES
YESYES
Modulation Delay
=<xx xx>Sec
Drive Sleeve
Close:
<cw or ccw>
<pos or trq>
Seat
Increment thru control mode
choices: 2 WIRE, 3 WIRE, 4 WIRE
IRDA, 3 WIRE Analog, Analog,
or Network
NO
or
NEXT
NO
NO
BACK
NEXT
BACK
SAVE CHANGE
SETTINGS?
VALVE CONTROL
SETUP?
Increment from 0.1 to 5.0%
in 0.1% Steps
Increment from 0.1 to 5.0%
in 0.1% Steps
Increment from 0.00 to
60.00 sec in 0.25 sec steps
Increment direction choice:
cw or ccw
NO NO NO NO NO
YES
Torque Backseat
<on/off>
YES
Close Torque
<xx>%
YES
Open Torque
<xx>%
Local Control
<LocalCtrlSetting>
Remote Control
<RemoteCtrlSetting>
Increment torque
backseat choice:
On or OFF
Increment close torque
percent: 15 to 100% in 1% steps
(limited by factory MAX
torque setting)
Increment local control
setting:
momentary or maintained
Increment remote control
setting:
momentary or maintained
Increment seat choice:
Position or Torque
Increment open torque
percent: 15 to 100% in 1% steps
(limited by factory MAX
torque setting)
NO NO NO NO
YES
Torque Retry
<on/off>
YES
Remote Display 1
<on/off>
YES YES
Remote Display 2
<on/off>
Close LED <color>
Open LED <color>
Increment torque
retry choice:
On or OFF
Increment remote
display 1 choice:
On or O
Change LED color choice:
close GREEN/open RED
close Red/open Green
Increment remote
display 2 choice:
On or O
NO NO
NO
NO NO NO
Valve Stall
Delay Time
<xx>
YES
YES YES YES
Retain Setpoint
<on/off>
Clear Alarm
Log?
Reset
Operation Log
Archive Torque
Profile
Increment from 1 to 60
in step size of 1
Between
On and O
Reset the
operations log
Archinve the
torque prole
Clear
the alarm
logs

Table of Contents