EasyManua.ls Logo

Emerson Bettis 500 - Network Controlled; Table 3-1 Connecting Actuator a to Actuator B

Emerson Bettis 500
102 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
February 2018
Installation and Operation Manual
E2K-405-0218 Rev. 2
22
Section 3: Installation
Installation
3.6.3 Network Controlled
For the actuator to be network controlled, a Controlinc ACM and a Communication
Adapter Module (CAM) must be installed. Each CAM is required for a specic
protocol and network topology, and enables the network capability. To install the
Controlinc ACM see Section 3.6.1, Wiring the ACM.
NOTE:
Factory personnel must install the ACM and CAM. These modules (CAMs) may be
installed in the eld only by factory-trained technicians using a special passcode to
enter the “FACTORY SETUP” mode.
Connect the actuators as shown in Table 3-1 for RS-485 redundant bus or E>Net
networks. If another protocol is selected then refer to the wiring diagram supplied
with the actuator for connections.
NOTE:
If E>Net network topology is specied, insert a jumper between Terminals 40 and
42 to connect the network cable shield throughout the network and connect a
single point earth/ground elsewhere.
See Section 3.3, Electrical Connections for general electrical
connection requirements.
Table 3-1. Connecting Actuator A to Actuator B
Terminal Block Function
39 Data Port A (+)
41 Data Port A (-)
40 Shield
43 Data Port B (+)
44 Data Port B (-)
42 Shield

Table of Contents

Related product manuals