Section 4: Operation
Operation
Two-Speed Timer Default Conguration
Close Open Anti-Water Hammer
Mode = OFF Mode = OFF Mode = OFF
Start Position = 30% Start Position = 70% Start Position = 10%
Stop Position = 1% Stop Position = 99%
Pulse ON time = 3.5 Sec Pulse ON time = 3.5 Sec Pulse ON time = 3.5 Sec
Pulse OFF time = 5.0 Sec Pulse OFF time = 5.0 Sec Pulse OFF time = 5.0 Sec
Auxiliary Control Module (ACM) Default Conguration
Analog Control - Futronic Network Control - Controlinc
Control Bandwidth = 2.0% Network Node Address = 001
Speed Bandwidth = 5.0% Response Delay Time = 8ms
Delay Time = 1 Second Parity = NONE
Input Polarity CLOSE = 4mA Analog I/0 Scale 0 - 4095
Output Polarity CLOSE = 4mA Write Protect = NO
STAYPUT on lost signal
1. Enter “SETUP” mode as detailed in Step No 2 of Section 2, Quick Start.
2. Place the selector knob in the NEXT position to advance through each
display until “DISPLAY SETTINGS?” is displayed.
3. Rotate the control knob to YES.
4. Scan through each display selecting NO or YES and BACK or NEXT as
needed to review the current settings. See Figure 4-4.
NOTE:
The “DISPLAY SETTINGS?” mode can be accessed without entering a passcode;
however no changes can be made to the settings in this mode. To make any
changes see Section 5, Customizing Actuator Settings.