structure
Keypad and
format
Advanced
parameter
descriptions
Serial comms
5.8
Menu
7:
Analog
I/O
Hardware
The drive has three analog inputs (AI1 to AI3) and two analog outputs (AO1 and AO2). Each input has a similar parameter structure and each output
has a similar parameter structure. The nominal full scale level for inputs in voltage mode is 10 V. This ensures that when the input is driven from a
Update
rate
The analog inputs are sampled every 4 ms except where the destinations shown in the table below are chosen, the input is in voltage mode and other
the output operates in voltage mode, is updated every 250 s, special scaling is used as described in the table and the user scaling is ignored.
108
Mentor MP Advanced User Guide
www.onxcontrol.com
Issue Number: 4
Input
destination