15.6 Density measurement problems
15.6.1 Erratic density reading
Cause
Normal process noise
Two-phase flow
Line pressure too low
The flow rate is too high for the installation
Pipe diameter too small
Contaminants or suspended solids in the process gas
Contaminants or suspended solids in the process fluid
Vibration in the pipeline
Erosion or corrosion
Recommended actions
1. Check your process conditions against the values reported by the device.
2. Increase the density damping value.
3. Decrease the flow rate.
4. Check for two-phase flow.
5. Ensure that line pressure or sample pressure meets installation requirements.
6. Increase back pressure to minimize bubble formation.
7. Minimize vibration in the pipeline.
8. Increase the pipe diameter.
9. Install a flow control method (bypass, flow chamber, expander, etc.).
10. Perform Smart Meter Verification.
15.6.2 Inaccurate density reading
Cause
Problem with process fluid
Incorrect density calibration factors
Wiring problem
Incorrect grounding
Two-phase flow
Plugged or coated sensor tube
Incorrect sensor orientation
RTD failure
Troubleshooting Configuration and Use Manual
April 2019 MMI-20048166
176 Micro Motion 4200 Transmitters