Option Description
Temperature-corrected
volume flow
The totalizer or inventory will track Temperature-Corrected Volume Flow
Rate and calculate total volume since the last reset.
Standard volume flow The totalizer or inventory will track Standard Volume Flow Rate and
calculate total volume since the last reset.
Net mass flow The totalizer or inventory will track Net Mass Flow Rate and calculate total
mass since the last reset.
Net volume flow The totalizer or inventory will track Net Volume Flow Rate and calculate
total volume since the last reset.
Note
The totalizer/inventory value will not automatically be reset when the source is changed. The user must
manually reset the totalizer/inventory.
Tip
If you are using the API referral application and you want to measure batch-weighted average density
or batch-weighted average temperature, you must have a totalizer configured to measure
temperature-corrected volume flow.
3. Set Totalizer Direction to specify how the totalizer or inventory will respond to forward or reverse flow.
Option Flow direction Totalizer and inventory behavior
Forward Only Forward Totals increment
Reverse Totals do not change
Reverse Only Forward Totals do not change
Reverse Totals increment
Bidirectional Forward Totals increment
Reverse Totals decrement
Absolute Value Forward Totals increment
Reverse Totals increment
Important
Actual flow direction interacts with Sensor Flow Direction Arrow to determine the flow direction that
the transmitter uses in processing. See the following table.
Table 6-1: Interaction between actual flow direction and Sensor Flow Direction Arrow
Actual flow direction Setting of Sensor Flow Direction
Arrow
Flow direction sent to outputs
and totalizers
Forward (same direction as Flow
arrow on sensor)
With Arrow Forward
Against Arrow Reverse
Reverse (opposite from Flow arrow
on sensor)
With Arrow Reverse
Configure advanced options for process measurement Configuration and Use Manual
April 2019 MMI-20048166
74 Micro Motion 4200 Transmitters