ZX Platform Condensing Unit
22
Check Running Hours of Each Compressor and Reset Operation Time After Compressor Replacement
Press and release
SEtC value
Flashing
Press to select compressor number
Press and hold SET key
SEtC value
Flashing
SEtC value
Flashing
Press or wait for 30 sec
Reset Parameters by Using ‘Hot Key’
Power off the unit
Insert the factory programmed ‘Hot Key’ into the 5pin connecter
Power on the unit
Factory programmed parameters will be copied from “Hot Key” to controller
doL’ message will blink and then ashing ‘End’ will be shown on the LED.
After 10sec, unit will run with new parameters
Remove ‘Hot Key’ from electronic controller
Save Parameters in ‘Hot Key’
Power on the unit
Insert ‘Hot key’ and press
key
Factory programmed parameters will be copied to ‘Hot Key’
‘uPL’ message will blink and then ashing ‘End’ will be shown on the LED.
Press
key and ‘End’ will stop ashing
Power off unit and remove ‘Hot key’ from controller
Power on unit
Digital scroll compressor controller has been specially developed for Emerson ZXD condensing unit. This controller is only intended
for use in Emerson ZXD condensing units, therefore Emerson has no responsibility of any use on other condensing unit.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Emerson ZX Platform Condensing Unit and is the answer not in the manual?

Emerson ZX Platform Condensing Unit Specifications

General IconGeneral
BrandEmerson
ModelZX Platform Condensing Unit
CategoryAir Conditioner
LanguageEnglish

Related product manuals