Cerabar M, Deltabar M, Deltapilot M Commissioning with the FF configuration program
Endress+Hauser 143
Pressure unit selection (Pressure Transducer Block)
Parameter name Description
Calibration Units/
CAL_UNIT
Entry
Index: 19
Data type: unsigned16
Access: OOS
Select the pressure unit.
If a new pressure unit is selected, all pressure-specific parameters are converted
and displayed with the new unit.
Options
• mbar, bar
•mmH
2
O, mH
2
O, inH
2
O, ftH
2
O
• Pa, hPa, kPa, MPa
•psi
•mmHg, inHg
•Torr
•g/cm
2
, kg/cm
2
•lb/ft
2
•atm
•gf/cm
2
, kgf/cm
2
Factory setting:
mbar or bar depending on the sensor nominal measuring range, or as per order
specifications