Commissioning with an operating menu (onsite display/FieldCare) Cerabar M, Deltabar M, Deltapilot M
116 Endress+Hauser
8.11 Description of parameters
This section describes the parameters in the order they are arranged in the "Expert" operating
menu.
Expert
8.11.1 System
Expert System
Parameter name Description
Direct access (119)
Entry
Enter the direct access code to go directly to a parameter.
Options:
A number between 0 and 999 (only valid entries are recognized)
Factory setting:
0
Note:
For direct access, it is not necessary to enter leading zeros.
Parameter name Description
Code definition (023)
Entry
Use this function to enter a release code with which the device can be unlocked.
Options:
A number between 0 and 9999
Factory setting:
0
Lock switch (120)
Display
Displays the status of DIP switch 1 on the electronic insert.
You can lock or unlock parameters relevant to the measured value with DIP switch
1. If operation is locked by means of the "Operator code (021)" parameter, you can
only unlock operation again by means of this parameter.
Display:
On (locking switched on)
Off (locking switched off)
Factory setting:
Off (locking switched off)
Operator code (021)
Entry
Use this function to enter a code to lock or unlock operation.
Options:
•To lock: Enter a number the release code.
To unlock: Enter the release code.
The release code is "0" in the order configuration. Another release code can be
defined in the "Code definition (023)" parameter. If the user has forgotten the
release code, it can be made visible again by entering the number sequence "5864".
Factory setting:
0