Operation Cerabar M, Deltabar M, Deltapilot M
46 Endress+Hauser
6.2 Operation without an operating menu
6.2.1 Position of operating elements
The operating key and DIP switches are located on the electronic insert in the device.
A0023127
Fig. 24: FOUNDATION Fieldbus electronic insert
1 Operating key for position zero adjustment (Zero) or reset
2 Green LED to indicate successful operation
3 Slot for optional local display
4+5 DIP switch only for Deltabar M
Switch 5: "SW/Square root"; used to control the output characteristics
Switch 4: "SW/P2-High"; used to determine the high-pressure side
6 DIP-switch for simulation mode
7 DIP switch for switching damping on/off
8 DIP switch for locking/unlocking parameters relevant to the measured value
Function of the DIP switches
on
off
SW / P2=High
Simulation
SW /
damping
1
2
345
on
off
Display
Zero
simulation
TM
F
OUNDATION
SW / P2=High
SW /
damping
delta p only
87654
1
2
3
Switche
s
Symbol/
labeling
Switch position
"off" "on"
1 The device is unlocked.
Parameters relevant to the measured
value can be modified.
The device is locked.
Parameters relevant to the measured
value cannot be modified.
2damping Damping is switched off.
The output signal follows measured value
changes without any delay.
Damping is switched on.
The output signal follows measured value
changes with the delay time .
1)
1) The value for the delay time can be configured via the operating menu ("Setup" -> "Damping").
Factory setting: = 2 s or as per order specifications.
3 Simulation The simulation mode is switched off
(factory setting).
The simulation mode is switched on.
The following switches only for Deltabar M:
4SW/ The output characteristics is defined by
the setting in the operating menu.
"Setup" -> "Measuring mode"
"Setup" -> "Extended setup" ->
The measuring mode is "flow" and the
output characteristics is "Square root"
regardless of the settings in the operating
menu.
5 SW/P2= High The high-pressure (+/HP) side is defined
by the setting in the operating menu.
("Setup" -> "High Press. Side")
The high-pressure side (+/HP) is
allocated to the P2 pressure connection
regardless of the setting in the operating
menu.