Deltabar FMD71, FMD72
Endress+Hauser 23
Total performance
The "Total performance" specification comprises the non-linearity including hysteresis, non-
reproducibility as well as the thermal change of the zero point. All specifications apply to the
temperature range –10 to +60 °C (+14 to +140 °F).
Measuring cell % of URL for every sensor Calculated total performance (TP
Diff
) of the differential pressure
400 mbar (6 psi) TP = ±0.25
TP = ±0.34
1)
Calculation (mbar, bar or psi):
TP
Diff
HP HP
2
(TP URL )
+=
.
LP LP
2
(TP URL )
.
100 100
A0016470
Percentage calculation of URL dP:
TP [%]
P
100
.
Diff
Diff
=
TP
Diff
A0016471
1 bar (15 psi)
2 bar (30 psi)
4 bar (60 psi)
10 bar (150 psi)
40 bar (600 psi)
TP = ±0.15
TP = ±0.25
1)
1) For hygienic process connections
The "Applicator Sizing Electronic dp" selection tool, available free of charge on the Endress
+Hauser web site (www.endress. com/applicator), enables detailed calculations for your
respective applications.
Long-term stability
'
1 year 5 years 10 years Calculated long-term stability (L
Diff
)
of the differential pressure
Measuring ranges % of URL for every sensor
400 mbar (6 psi) L = ±0.035
L = ±0.25
1)
L = ±0.14 L = ±0.32 Calculation (mbar, bar or psi):
L
Diff
HP HP
2
(L
100 100
URL )
+=
.
LP LP
2
(L URL )
.
A0016463
Percentage calculation of URL dP/year:
A0016464
1 bar (15 psi) L = ±0.020
L = ±0.1
1)
L = ±0.08 L = ±0.180
2 bar (30 psi)
4 bar (60 psi)
10 bar (150 psi)
L = ±0.025
L = ±0.1
1)
L = ±0.05 L = ±0.075
40 bar (600 psi) L = ±0.025
L = ±0.1
1)
L = ±0.075 L = ±0.100
1) For hygienic process connections
Total error
The total error comprises the total performance and long-term stability. All specifications apply to
the temperature range –10 to +60 °C (+14 to +140 °F).
Measuring cell % of URL/year for every sensor Calculated total error (TE
Diff
) of the differential pressure
400 mbar (6 psi) TE = ±0.30 Calculation (mbar, bar or psi):
TE
Diff
HP HP
2
(TE URL )
+=
.
LP LP
2
(TE URL )
.
100 100
A0016472
Percentage calculation of URL dP:
TE [%]
P
100
.
Diff
Diff
=
TE
Diff
A0016473
1 bar (15 psi)
2 bar (30 psi)
4 bar (60 psi)
10 bar (150 psi)
40 bar (600 psi)
TE = ±0.20
Warm-up period
4 to 20 mA HART : < 10 s