Deltabar FMD71, FMD72
Endress+Hauser 25
Installing the sensor
modules
General installation instructions
• Due to the orientation of the sensor modules, there may be a shift in the zero point, i.e. when the
vessel is empty or partially full, the measured value does not display zero.
• Always install the sensor module HP below the lowest measuring point.
• Always install the sensor module LP above the highest measuring point.
• Do not mount the sensor modules in the filling curtain or at a point in the tank which could be
affected by pressure pulses from an agitator.
• Do not mount the sensor modules in the suction area of a pump.
• The adjustment and functional test can be carried out more easily if you mount the sensor
modules downstream of a shutoff device.
Mounting sensor modules
with PVDF installation
coupling
L
WARNING
Risk of damage to process connection!
Risk of injury!
‣
Sensor modules with PVDF process connections with threaded connection must be installed with
the mounting bracket provided!
The mounting bracket can be installed on pipes with a diameter of 1¼" to 2" or on walls.
A0017514
• The mounting bracket is included in the delivery.
• Ordering information:
Product Configurator order code for "Enclosed accessories", option "PA" or
as separate accessory (Part No.: 71102216).
• Dimensions → 54.
Installing the transmitter
The transmitter is installed with the mounting bracket supplied. The mounting bracket can be
installed on pipes with a diameter of 1¼" to 2" or on walls.
A0021145
• The mounting bracket is included in the delivery.
• If an additional mounting bracket is required, this can be ordered as follows:
Product Configurator order code for "Enclosed accessories", option "PA" or as separate accessory
(part number: 71102216).
• Dimensions → 54.