Commissioning Deltabar PMD75B PROFINET with Ethernet-APL
54 Endress+Hauser
Example: Outputting of the flow value at the current output
In the following example, the flow value should be measured and output at the current
output.
Perform position adjustment if necessary
Output the flow signal 0 to 100 m
3
/h as a 4 to 20 mA value
100 m
3
/h corresponds to 30 mbar (0.435 psi)
Menu path: Guidance → Commissioning
In the Assign PV parameter, select the Scaled variable option
In the Pressure unit parameter and Scaled variable unit parameter, select the desired
unit
In the Output current transfer function parameter, select the Square option
Pressure value 1 parameter / Scaled variable value 1 parameter
Enter 0 mbar (0 psi) / 0 m
3
/h
Pressure value 2 parameter / Scaled variable value 2 parameter
Enter 30 mbar (0.435 psi) / 100 m
3
/h
Proceed as follows if the flow does not have to be displayed as a measured value and only a
square root extraction should be output.
Menu path: Guidance → Commissioning
In the Assign PV parameter, select the Pressure option
In the Output current transfer function parameter, select the Square option
In the Lower range value output parameter, enter 0 mbar (0 psi)
In the Upper range value output parameter, enter 30 mbar (0.435 psi)