Deltapilot S FMB70 Commissioning (installation and configuration)
Endress+Hauser 13
Parameter Available in the operating mode Group
Pressure Level, level selection
"Level easy pressure"
MEASURING MODE X X MEASURING MODE
EMPTY PRESSURE X BASIC SETUP
EMPTY CALIB. X BASIC SETUP
FULL PRESSURE X BASIC SETUP
FULL CALIB. X BASIC SETUP
SET LRV X X BASIC SETUP
SET URV X X BASIC SETUP
DAMPING VALUE X X BASIC SETUP
OUTPUT FAIL MODE
1)
X X OUTPUT
SET MIN. CURRENT
1)
X X OUTPUT
SET MAX. ALARM
1)
X X OUTPUT
1) From firmware version ≥2.30
The EMPTY PRESSURE and FULL PRESSURE parameters are only displayed for the
"Dry" CALIBRATION MODE. If you have performed a wet calibration, you must
subsequently select the "Dry" option via the CALIBRATION MODE parameter. You can
read out the corresponding values for the EMPTY PRESSURE and FULL PRESSURE
parameters here.
4. Switch the device off and then on again. This ensures that the parameter settings are
saved.
5. Check the safety function.
6. Select the "SAFETY CONFIRM." group (menu path: (GROUP SELECTION→)
OPERATING MENU → SAFETY CONFIRM.)
7. Select the "Lock" option. Select the "Lock" option via the SAFETY LOCK parameter. The
status "Locked" or "Unlocked" is indicated on the fourth line of the display.
8. Enter the password via the SAFETY PASSWORD parameter (password: 7452)
For firmware version ≤02.20.04
• If the correct password is entered, the following parameters are reset to the factory
values (→ Step 10 for factory values):
• CURRENT CHARACT.
• OUTPUT FAIL MODE
• ALT. CURR. OUTPUT
• SET MAX. ALARM
• SET MIN. CURRENT
• SIMULATION MODE
• ALARM DELAY
• ALARM DISPLAY TIME
• SELECT ALARM TYPE
• Any simulation which may be running is ended
• The configurable messages ("Error"-type messages) 115, 120, 620, 715, 717, 718, 720,
726 and 727 are automatically set to "Alarm" ("Messages" section of the relevant
Operating Instructions)