Deltapilot S FMB70 Commissioning (installation and configuration)
Endress+Hauser 15
• OUTPUT FAIL MODE
• SET MIN. CURRENT
• SET MAX. ALARM
The value saved is indicated on the fourth line of the local display.
Options:
• Valid: Select this option if the entered value or the desired value is displayed. The device
continues to interrogate the safety-related parameters.
• Not valid: Select this option if an incorrect value or a value that was not entered is
displayed. In this case, operation in the safe measuring mode is not possible. The
SAFETY LOCK parameter displays the status "Unlocked". The confirmation sequence is
cancelled.
12. Once the safety-related parameters have been successfully interrogated, the
password "7452" must be entered again via the CONF. PASSWORD parameter.
Afterwards, the device is locked for the safe measuring mode. The SAFETY LOCK
parameter displays the status "Locked". This locking has the highest priority and can
only be disabled via the SAFETY LOCK and SAFETY PASSWORD parameters.
Parameter configuration via Field Communicator 375/475 handheld terminal
1. Go to "Main Menu" → "HART Communication" → "HART-Application" → "Online". The
device is then found automatically and opened online. Ensure that the device bus
address = 0.
2. Ensure that the connection has been made with the correct device. This can be done
using the "Measuring point" parameter, the extended order number or the serial
number.
3. Reset parameters to factory setting: reset code "7864" (see the associated Operating
Instructions, "Resetting to factory setting (reset)" section). Check default values,
number formats and parameter descriptions with the "Device parameter
configuration report".
4. Configure the device.
5. Enter the settings for the following parameters according to the report, since these
settings are queried for safe device configuration.
Parameter Available in the operating mode Group
Pressure Level, level selection
"Level easy pressure"
ACK. ALARM MODE X X MESSAGES
CALIB. OFFSET X X POSITION ADJUST.
MEASURING MODE X X MEASURING MODE
EMPTY PRESSURE X BASIC SETUP
EMPTY CALIB. X BASIC SETUP
FULL PRESSURE X BASIC SETUP
FULL CALIB. X BASIC SETUP
SET LRV X X BASIC SETUP
SET URV X X BASIC SETUP
DAMPING VALUE X X BASIC SETUP
OUTPUT FAIL MODE
1)
X X OUTPUT