Commissioning (installation and configuration) Deltapilot S FMB70
16 Endress+Hauser
Parameter Available in the operating mode Group
Pressure Level, level selection
"Level easy pressure"
SET MIN. CURRENT
1)
X X OUTPUT
SET MAX. ALARM
1)
X X OUTPUT
1) From firmware version ≥2.30
The EMPTY PRESSURE and FULL PRESSURE parameters are only displayed for the
"Dry" CALIBRATION MODE. If you have performed a wet calibration, you must
subsequently select the "Dry" option via the CALIBRATION MODE parameter. You can
read out the corresponding values for the EMPTY PRESSURE and FULL PRESSURE
parameters here.
6. Switch the device off and then on again. This ensures that the parameter settings are
saved.
7. Check the safety function.
8. Close the Field Communicator 375/475 handheld terminal. Then connect to the
device again.
9. Select the "SAFETY CONFIRM." group (menu path: (GROUP SELECTION→)
OPERATING MENU → SAFETY CONFIRM.)
10. Select the "Lock" option. Select the "Lock" option via the SAFETY LOCK parameter. The
status "Locked" or "Unlocked" is indicated on the fourth line of the display.
11. Enter the password via the SAFETY PASSWORD parameter (password: 7452)
For firmware version ≤02.20.04
If the correct password is entered, the following parameters are reset to the factory
values (→ Step 10 for factory values):
CURRENT CHARACT.
OUTPUT FAIL MODE
ALT. CURR. OUTPUT
SET MAX. ALARM
SET MIN. CURRENT
SIMULATION MODE
ALARM DELAY
ALARM DISPLAY TIME
SELECT ALARM TYPE
Any simulation which may be running is ended
The configurable messages ("Error"-type messages) 115, 120, 620, 715, 717, 718, 720,
726 and 727 are automatically set to "Alarm" ("Messages" section of the relevant
Operating Instructions)
For firmware version ≥02.30.zz
Any simulation which may be running is ended
No parameters are reset
Log the following confirmed settings according to the "Device parameter configuration
report".
12. Via the DIGIT SETS parameter, the user can check whether the characters and digits
are displayed correctly on the user interface. "0123456789.-" is shown if everything is
displayed correctly. Options: Valid: Select this option if the string of characters and
digits is displayed correctly. Not valid: Select this option if the string of characters and
digits is not displayed correctly. In this case, operation in the safe measuring mode is
not possible. The confirmation sequence is cancelled.