Deltapilot S FMB70 Commissioning (installation and configuration)
Endress+Hauser 17
13. Only for firmware version ≤02.20.04: Via the OUTPUT CURRENT parameter, the user
can check whether the following parameters are correctly reset to the factory values.
If reset correctly, the OUTPUT CURRENT parameter displays
"LinMaxNorm/22/3.8/0s".
Factory values:
• CURRENT CHARACT.: Linear
• OUTPUT FAIL MODE: Max. alarm
• ALT. CURR. OUTPUT: Normal
• SET MAX. ALARM: 22 mA
• SET MIN. CURRENT: 3.8 mA
• ALARM DELAY: 0.0 s
• ALARM DISPLAY TIME: 0.0 s
Options:
• Valid: Select this option if the factory values displayed correspond to the desired values.
The device continues to interrogate the safety-related parameters.
• Not valid: Select this option if the factory values displayed do not correspond to the
desired values. In this case, operation in the safe measuring mode is not possible. The
SAFETY LOCK parameter displays the status "Unlocked". The confirmation sequence is
cancelled.
14. Depending on the selected operating mode, the following parameters must be
confirmed:
For firmware version ≤02.20.04
• ACK. ALARM MODE
• CALIB. OFFSET
• MEASURING MODE
• EMPTY PRESSURE (only Level operating mode)
• EMPTY CALIB. (only Level operating mode)
• FULL PRESSURE (only Level operating mode)
• FULL CALIB. (only Level operating mode)
• SET LRV
• SET URV
• DAMPING VALUE
For firmware version ≥02.30.zz
• ACK. ALARM MODE
• CALIB. OFFSET
• MEASURING MODE
• EMPTY PRESSURE (only Level operating mode)
• EMPTY CALIB. (only Level operating mode)
• FULL PRESSURE (only Level operating mode)
• FULL CALIB. (only Level operating mode)
• SET LRV
• SET URV
• DAMPING VALUE
• OUTPUT FAIL MODE
• SET MIN. CURRENT
• SET MAX. ALARM
The value saved is indicated on the fourth line of the local display.
Options:
• Valid: Select this option if the entered value or the desired value is displayed. The device
continues to interrogate the safety-related parameters.
• Not valid: Select this option if an incorrect value or a value that was not entered is
displayed. In this case, operation in the safe measuring mode is not possible. The
SAFETY LOCK parameter displays the status "Unlocked". The confirmation sequence is
cancelled.