30
Nivotester FTR525
Endress+Hauser
Commissioning
038
1M
2
1
3
4
19 Manualadjustmentupperlimit(UL)
1 Currentmeasuredvalue
2 Setdetectionrange(=0-100%ofsignaloutput)
3 Percentagevaluefortheupperlimitrelativetothemaximumpossibledetectionrange
4 Upperlimit(adjustableusingthisfunction)
8�4�1�4 Level limit detection damping
Application
2000
→
Sensor
2100
→
Limit detection
2110
→
Damping
2114
It is possible, for instance in the case of very turbulent processes, to steady the measuring
signal. To do so, a time can be set over which the measured values are averaged.
Setting the damping results in a longer reaction time.
8�4�1�5 Automatic setup of motion detection
Application
2000
→
Sensor
2100
→
Motion detection
2120
→
Automatic setup
2121
Automatic setup is carried out with movement of bulk solids either present or not
present (in front of the FDR57 transceiver); the option selected for this corresponds to the
Options: "With movement", "Without movement"
1 2
FQR57 FDR57
FQR57 FDR57
20 Setupconditionsofthemotiondetection
the microwave barrier or to suit changing application conditions.
8.4.1.6 Manualadjustmentlowerlimit(LL)motiondetection
Application
2000
→
Sensor
2100
→
Motion detection
2120
→
Manual adjustment LL
2122
This function can be used to change the lower limit of the set detection range of the
motion detection (function 2112