8�4�2�8 Fixed value for the current output in the event of an error
Application
2000
→
Current output
2300
→
Fixed value
2350
This function is used to enter the current value to be put out in the event of an error while
"Fixed value" is selected in function 2310.
Options: 3.6 to 22.0 mA
8.4.2.9 Switchingfunctionswitchingoutput1
Application
2000
→
Switchingoutputs
2400
→
Switchingoutput1
2410
→
Switchingfunctionoutput1
2411
Options: "Min.safety", "Max.safety"
8�4�2�10 Switch-onpointswitchingoutput1
Application
2000
→
Switchingoutputs
2400
→
Switchingoutput1
2410
→
Switch-onpointoutput1
2412
In this function the switching point of signal output 1, above which the switching output
Options: 0 to 100 %
Switching output
is activated
Switching output
is deactivated
Grenzstand 1
070
2 4 1 2
▴▴
Function
2413
Function
2412
25 Switchpointsofoutput1
8�4�2�11 Switch-opointswitchingoutput1
Application
2000
→
Switchingoutputs
2400
→
Switchingoutput1
2410
→
Switch-opointoutput1
2413
In this function the switching point of signal output 1, below which the switching output
Options: 0 to 100 %
2412), the switching hysteresis is therefor zero.