Commissioning
8�4�2�8 Fixed value for the current output in the event of an error
Application
2000
Current output
2300
Fixed value
2350
This function is used to enter the current value to be put out in the event of an error while
"Fixed value" is selected in function 2310.
Options: 3.6 to 22.0 mA
8.4.2.9 Switchingfunctionswitchingoutput1
Application
2000
Switchingoutputs
2400
Switchingoutput1
2410
Switchingfunctionoutput1
2411

Options: "Min.safety", "Max.safety"
8�4�2�10 Switch-onpointswitchingoutput1
Application
2000
Switchingoutputs
2400
Switchingoutput1
2410
Switch-onpointoutput1
2412
In this function the switching point of signal output 1, above which the switching output


Options: 0 to 100 %
Switching output
is activated
Switching output
is deactivated
Grenzstand 1
070
2 4 1 2
Function
2413
Function
2412
25 Switchpointsofoutput1
8�4�2�11 Switch-opointswitchingoutput1
Application
2000
Switchingoutputs
2400
Switchingoutput1
2410
Switch-opointoutput1
2413
In this function the switching point of signal output 1, below which the switching output


Options: 0 to 100 %

2412), the switching hysteresis is therefor zero.