Proline Promag H 300
Endress+Hauser 15
Maximum switching
capacity (passive)
DC 30 V, 0.1 A
AC 30 V, 0.5 A
Assignable functions Off
On
Diagnostic behavior
Limit value:
Off
Volume flow
Mass flow
Corrected volume flow
Flow velocity
Conductivity
Corrected conductivity
Totalizer 1-3
Temperature
Electronic temperature
Flow direction monitoring
Status
Empty pipe detection
Low flow cut off
User configurable input/output
One specific input or output is assigned to a user-configurable input/output (configurable I/O)
during device commissioning.
The following inputs and outputs are available for assignment:
Choice of current output: 4 to 20 mA (active), 0/4 to 20 mA (passive)
Pulse/frequency/switch output
Choice of current input: 4 to 20 mA (active), 0/4 to 20 mA (passive)
Status input
The technical values correspond to those of the inputs and outputs described in this section.
Signal on alarm
Depending on the interface, failure information is displayed as follows:
HART current output
Device diagnostics Device condition can be read out via HART Command 48
PROFIBUS PA
Status and alarm
messages
Diagnostics in accordance with PROFIBUS PA Profile 3.02
Error current FDE (Fault
Disconnection Electronic)
0 mA
FOUNDATION Fieldbus
Status and alarm
messages
Diagnostics in accordance with FF-891
Error current FDE (Fault
Disconnection Electronic)
0 mA
Modbus RS485
Failure mode Choose from:
NaN value instead of current value
Last valid value