Proline Promag H 300
Endress+Hauser 27
Connection examples
Current output 4 to 20 mA HART
4
4...20 mA
5
2
1
3
6
A0029055
 2 Connection example for 4 to 20 mA HART current output (active)
1 Automation system with current input (e.g. PLC)
2 Cable shield: the cable shield must be grounded at both ends to comply with EMC requirements; observe cable
specifications →  34
3 Connection for HART operating devices →  82
4 Resistor for HART communication (≥ 250 Ω): observe maximum load →  12
5 Analog display unit: observe maximum load →  12
6 Transmitter
2
3
4...20 mA
41
5
A0028762
 3 Connection example for 4 to 20 mA HART current output (passive)
1 Automation system with current input (e.g. PLC)
2 Power supply
3 Cable shield: the cable shield must be grounded at both ends to comply with EMC requirements; observe cable
specifications →  34
4 Analog display unit: observe maximum load →  12
5 Transmitter