Technical data Proline Promass F 100 Modbus RS485
98
Low flow cut off The switch points for low flow cut off are user-selectable.
Galvanic isolation The following connections are galvanically isolated from each other:
Outputs
Power supply
Protocol-specific data
Protocol Modbus Applications Protocol Specification V1.1
Device type Slave
Slave address range 1 to 247
Broadcast address range 0
Function codes 03: Read holding register
04: Read input register
06: Write single registers
08: Diagnostics
16: Write multiple registers
23: Read/write multiple registers
Broadcast messages Supported by the following function codes:
06: Write single registers
16: Write multiple registers
23: Read/write multiple registers
Supported baud rate 1 200 BAUD
2 400 BAUD
4 800 BAUD
9 600 BAUD
19 200 BAUD
38 400 BAUD
57 600 BAUD
115 200 BAUD
Data transfer mode ASCII
RTU
Data access Each device parameter can be accessed via Modbus RS485.
For Modbus register information, see "Description of device parameters"
documentation
16.5 Power supply
Terminal assignment →  30
→  29
Pin assignment, device plug →  32
Supply voltage The power unit must be tested to ensure it meets safety requirements (e.g. PELV, SELV).
Transmitter
Modbus RS485, for use in non-hazardous areas and Zone 2/Div. 2:
DC 20 to 30 V
Modbus RS485, for use in intrinsically safe areas:
Power supply via Safety Barrier Promass 100