2 Installation
2.1 Transporting to the measuring point
Transport the measuring device to the measuring point in the original packaging.
The covers or caps fitted on the process connections prevent mechanical damage to the
sensors during transport and storage. For this reason, do not remove the covers or caps until
immediately before installation.
2.2 Installation conditions
The thermal dispersion principle is sensitive to disturbed flow conditions. Therefore, the
requirements and conditions for installation in this section are especially important
Take measures to reduce or avoid condensation (e.g. install a condensation trap, thermal
insulation, etc.).
2.2.1 Dimensions
For the dimensions of the measuring device see associated Technical Information on the
CD-ROM.
A0007408
Use slings around the process connections.
#
Warning!
Risk of injury! The device can slip.
The center of gravity of the measuring device may be
higher than the holding points of the slings.
Always ensure that the device cannot slip or turn around
its axis.
A0007409
Do not lift measuring devices by the transmitter housing
or the connection housing in the case of the remote
version. Do not use chains as they could damage the
housing.