2.2.4 Inlet/outlet runs
The thermal dispersion principle is sensitive to disturbed flow conditions.
As a general rule, the installed thermal flow sensor should always be installed as far away as
possible from any flow disturbances. Further information is provided in ISO Standard 14511.
m In the case of saturated or unclean gases, upward flow in a vertical pipe section is preferred to minimize
condensation/contamination.
n Not recommended if the vibrations are too high or if the installation is unstable.
o Only suitable for clean/dry gases. On horizontal pipes do not mount the sensor from the bottom, if the gas is very damp
or saturated with water (e. g. Bio Gas). Mount the sensor in a position as indicated below (α =135°).
A0009897
Flanged version
A0007523 A0007524 A0007525
A0007526 A0007527 A0007528
15xDN 2xDN
15xDN
2xDN
15xDN
2xDN
20xDN
2xDN
35xDN
2xDN
50xDN
2xDN