EasyManua.ls Logo

Endress+Hauser Prosonic S FMU90 PROFIBUS DP - Connection to a PROFIBUS DP Network

Endress+Hauser Prosonic S FMU90 PROFIBUS DP
110 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Prosonic S FMU90 PROFIBUS DP Electrical connection
Endress+Hauser 29
Display
POWER
HART
0/4…20mA
Sync
Fuse
I
1
FDU-
Sensor
RD
11
BK
10
YE
9
40
39
5
4
6
7
8
1
Service
Relay
2
1
3
1
L
N PE
2
90 253 VAC
10.5 32 VDC
3
4
A0035932
 24 Connection of the power supply in the DIN rail housing
1 Metal DIN rail in cabinet
2 Terminal strip (no contact to DIN rail)
3 Protective ground terminal strip (with contact to DIN rail)
4 Grounding via DIN rail
6.3.2 Connection to a PROFIBUS DP network
For information on the layout of a PROFIBUS DP network, see Operating Instructions
BA00034S, "PROFIBUS DP/PA - Guidelines for planning and commissioning"
Cable specification
For transmission rates up to 12 Mbit/s, use cable type A according to EN 50170.
Characteristic impedance: 135 to 165 Ω at a measuring frequency of 3 to 20 MHz
Cable capacitance: < 30 pF/m
Wire cross-section: > 0.34 mm
2
(22 AWG)
Wires: twisted pairs, 1x2, 2x2 or 1x4 conductors
Loop-resistance: 110 Ω/km
Signal attenuation: < 9 dB over the entire length of the cable segment
Shielding: copper braided shielding or braided shielding and foil shield
Pre-terminated cables are available from Endress+Hauser.
T-junction boxes
It is recommended to connect the Prosonic S using T-junction boxes.
Suitable junction boxes are available from Endress+Hauser.

Table of Contents