Electrical connection Prosonic S FMU90 PROFIBUS DP
30 Endress+Hauser
Spurs
Information regarding spurs
The cable between the connector and the bus driver in the field device is known as a
spur.
Total length of all spurs < 6.6 m (22 ft) at max. 1.5 Mbit/s.
Spurs may not have a bus terminator.
Spurs should not be used for transmission rates > 1.5 Mbit/s.
Practical experience in plants has shown that caution must be exercised when
configuring spurs. It cannot be assumed that the sum of all spurs at transmission rates of
1.5 Mbit/s may be 6.6 m (22 ft). This is greatly influenced by the actual arrangement of
the field devices.
6.3.3 Sensor connection
L
CAUTION
Inadequate potential equalization can compromise electrical safety
Connect the yellow/green protective ground of the FDU91F, FDU93 and FDU95
sensors to local potential equalization after a maximum distance of 30 m (98 ft). The
can be done in a terminal box, at the transmitter or in the cabinet.
NOTICE
Interference signals may cause malfunctions
Do not route the sensor cables parallel to high-voltage electric power lines or near
frequency converters.
NOTICE
A damaged cable shield may cause malfunctions
For pre-terminated cables: connect the black wire (shield) to the "BK" terminal.
For extension cables: twist the shield and connect to the "BK" terminal.
L
WARNING
Explosion Hazard
Do not connect FDU83, FDU84, FDU85 and FDU86 sensors with an ATEX, FM, or CSA
certificate to the FMU90 or FMU95 transmitters.
For the sensors FDU91F/93/95/96 and FDU83/84/85/86: connect the ground cable
(GNYE) to local potential equalization after a maximum distance of 30 m (98 ft). This
can be done in the terminal box or at the transmitter or in the cabinet if the distance to
the sensor does not exceed 30 m (98 ft).
NOTICE
The evaluation electronics and their direct connections (display/service connector,
service interface etc.) are galvanically isolated from the power supply and the
communication signals, and are connected to the potential of the sensor electronics.
Pay attention to the potential difference in the case of grounded sensors.
If removing the jacket of the sensor cable, take the longest required cable length into
consideration.
Further information and the documentation currently available can be found on
the Endress+Hauser website: www.endress.com → Downloads.
Sensor documentation:
TI01469F (FDU90)
TI01470F (FDU91)
TI01471F (FDU91F)
TI01472F (FDU92)
TI01473F (FDU93)
TI01474F (FDU95)
Sensors FDU80/80F/81/81F/82/83/84/85/86/96 can no longer be ordered. The
Prosonic S transmitter can still be connected if the sensors are already installed.