Prosonic S FMU90 PROFIBUS DP Electrical connection
Endress+Hauser 37
L
WARNING
Explosion Hazard
‣
Install the power supply unit outside the hazardous area.
‣
Use a cable that meets the requirements of the zone in which the aluminum field
housing is installed.
‣
Connect the sensor heater inside the aluminum field housing (or another explosion-
proof housing) to the power supply. To do so, install additional terminal blocks on the
DIN rail in the housing.
‣
Prior to opening the aluminum field housing: switch off the power supply to the sensor
heater.
24 VDC
FDU90
FDU91
+
-
BN
BU
-
.
FMU90
24 VDC
+
-
1
A0033332
31 Connection of the sensor heater in the aluminum field housing
1 External power supply unit
BN Brown wire
BU Blue wire
Connection of the sensor heater in the DIN rail housing
Valid for:
Order code 030 (housing, material)
Option 2 (DIN rail mounting PBT, IP20)
The supply voltage must be provided in the cabinet, e.g. via a terminal block: