Prosonic S FMU90 PROFIBUS DP Electrical connection
Endress+Hauser 43
Display
POWER
HART
0/4…20mA
Sync
Fuse
I
1
FDU-
Sensor
RD
11
BK
10
YE
9
40
39
5
4
6
7
8
Service
Relay
3
2
1
1
A0034903
 39 Connection of the remote display and operating module
1 Pre-terminated connecting cable 3 m (9.8 ft) with display plug (supplied)
Minimum diameter for cable entry
20 mm (0.79 in)
6.3.12 Post-connection check
 Is the terminal assignment correct?
For field housing (polycarbonate/aluminum):
 Are the cable glands tight?
 Is the housing cover securely closed?
For aluminum field housing:
 Is the housing connected to protective ground (PE) and/or the local ground potential
(PML)?
If the power supply is switched on:
 Is the LED for the operating state lit green?
 If a display module is attached: does anything appear on the screen?