Commissioning Prosonic S FMU90 PROFIBUS DP
58 Endress+Hauser
9.3.7 Parameter set "Check value"
This parameter set starts interference echo suppression (mapping).
To record all the interference echoes, perform mapping at the minimum level
possible (ideally in an empty channel).
If it is not possible to empty the channel during commissioning, record preliminary
mapping when the channel is partially filled. Repeat mapping when the level
reaches approximately 0% for the first time.
(a)
(b)
(c)
(a)
(b)
A
B
C
(a)
A0035533
 48 Operating principle of the interference echo suppression (mapping) function
A The echo curve (a) contains an interference echo and the level echo. Without mapping, the interference echo
might also be evaluated.
B Mapping generates the mapping curve (b). This suppresses all the echoes that are inside the range of
mapping (c).
C Afterwards, only echoes that are higher than the mapping curve are evaluated. The interference echo is below
the mapping curve and is therefore ignored (not evaluated).
Navigation
Basic setup → Check value
Parameters
Distance
Displays the distance D currently measured between the sensor membrane and the
surface of the liquid.
Check distance
Compare the distance displayed with the actual value and enter the result of the
comparison. Based on the entry, the device automatically determines the range of
mapping.
Distance = ok
The displayed distance and actual distance match.
→ Continue with the parameter set LVL N dist. map..
Dist. too small
The displayed distance is smaller than the actual distance.
→ Continue with the parameter set LVL N dist. map..
Dist. too big
The displayed distance is larger than the actual distance.
→ Mapping is not possible.
→ Setup for sensor N ends.
Dist. unknown
Actual distance is unknown.
→ Mapping is not possible.
→ Setup for sensor N ends.
Manual
The range of mapping is to be defined manually.
→ Continue with the parameter set LVL N dist. map..