Prosonic S FMU90 PROFIBUS DP Commissioning
Endress+Hauser 59
9.3.8 Parameter set "Distance mapping"
Navigation
Basic setup → Check value → Distance mapping
Parameters
Actual distance
Displays the distance D currently measured between the sensor membrane and the
surface of the liquid.
Range of mapping
Specifies the range, starting from the sensor membrane, in which mapping is performed.
If Check distance = Distance = Ok or Dist. too small:
Confirm the preset value.
If Check distance = Manual:
Enter the desired mapping range.
Start mapping
Select Yes to start recording the mapping curve.
→ The Flow N status parameter set appears.
→ If the displayed distance is still too small: keep recording mapping curves until the
displayed distance and the actual distance match.
Status
Specifies the mapping status:
Enable map
The mapping curve is taken into consideration during signal evaluation.
Disable map
The mapping curve is not taken into consideration during signal evaluation but
remains stored in the device.
Delete map
The mapping curve is deleted.
9.3.9 Parameter set "US sensor N"
For multi-channel devices: disable unused sensor inputs in the US sensor N
parameter set.
Navigation
Sensor management → FDU sensor N → Sensor operation
Parameter "Sensor operation"
Switch sensor N on or off.