Commissioning Prosonic S FMU90 PROFIBUS DP
64 Endress+Hauser
9.4.2 Configuring simultaneous level and flow measurement with
one sensor
L
Q(l/s)
L (m)
Q (l/s)
21
1
2
3 m
3
A0038435
51 Simultaneous level and flow measurement with one sensor
1 Sensor
2 Prosonic S transmitter
L Level
Q Flow
1. Navigate to: Device properties → Operating param. → Operating mode
2. Select the Level + flow option.
3. Switch to the Level menu. In this menu, configure level measurement, including
mapping.
4. Switch to the Flow menu. In this menu, configure flow measurement. It is not
necessary to configure mapping here.
9.4.3 Configuration of flow counter parameters
Navigation
• For totalizers (not resettable):
Flow → Flow counter → Flow counter N
• For daily counters (resettable)
Flow → Daily counter → Daily counter N
Parameter
• Allocation
Select the flow that is to be counted.
• Counter unit
Select the unit for counting.
• Value
Indicates the current value of the flow counter.
• Overflow
Indicates the number of times the counter has passed the overflow point.
Flow = (overflow x 10
7
+ value) x counter unit
• Reset
Only available on daily counters.
Select the Yes option to reset the counter.