Parameter Setting up selections
Default
settings
Actual
settings
Display value 100%
SCHI
Display value at 100%
sensor value
Value:
-999 to 9999
The scale is preset on
temperature measurement!
100,0
SC
HI
Offset
OFFS
Signal offset for matching
the measured value
display
Value:
-999 to 9999
0,0
OF
FS
Bargraph 0%
BGLO
Allocation of 0% bargraph
reading to measured value
Value: SCLO to SCHI
see example in chapter 6.3
0,0
BG
LO
Bargraph 100%
BGHI
Allocation of 100% bargraph
reading to measured value
Value: SCLO to SCHI
see example in chapter 6.3
100,0
BG
HI
* Comp. temperature
CMPT
Selection between
internal and external
comparison temperature
when using thermo-
couples. (Only with
“Universal input” option)
INT Internal comparison
temperature measured
using internal sensor
FIX Fixed comparison
temperature
INT
CM
PT
* Fixed
comparison temp.
FTMP
Input of the fixed
comparison temperature
for TC
(Only with “Universal
input” option and when in
CMPT FIX is set up)
Value:
0°C ... 80°C /
32°F...176°F
20
68
FT
MP
FT
MP
Square root
SQRT
The measured value from
sensors giving a squared
signal can be square root
extracted and then
displayed.
OFF Function not active
ON Function active
OFF
SQ
RT
End
END
End of setting up
parameters
Process display
46