8. Technical data
General
information
Unit function Process display for panel mounting.
Application Process display,
limit contactor
The display recieves an anlogue signal and shows the
corresponding value on the display.
Four presettable set points monitor the measured
value for any infringement of the preset conditions and
control the relays. Transmitters connected can be
directly powered by the unit.
Operating and
system
construction
Measurement
principle
The analogue signal connected is digitalised, analysed
and indicated in the display.
Measurement
system
Microcontroller controlled display with LC display,
analogue input, limit relays and loop power supply.
Input Input types Current, voltage, resistive thermometers (RTD),
thermocouple (TC).
Measurement
range
(Input current/
coltage)
Voltage: 0...1/10 V; max. 50 V Ri:1 MOhm
Current: 0/4...20 mA; max.100 mA Ri: 50 Ohm
Voltage: +/-20 mV, +/-50 mA, ±100 mV, ±200 mV,
±1 V, ±2 V, ±5 V, ±10 V, 0...1 V, 0...10 V,
max. ±50 V, Ri: 1 MOhm
Measurement
range (option
“Universal input”)
Current: 0/4...20 mA; max.100 mA Ri: 50 Ohm
RTD: Pt100, Pt500, Pt1000:
-100°C ... +600°C (DIN EN60751);
Ni100: -60°C...+180°C (DIN 43760);
Sensor current: approx. 1 mA; connection: 2-, 3-wire;
Cable compensation: To approx. 100 Ohm
TC: Type T: -270...+400°C Type J: - 210...+1200°C
Type K: -270...+1372°C Type R: -50...+1800°C
Type S: 0...+1800°C Type B: 200... +1820°C
Type N: -270...+1300°C Type U: -200...+60°C
Type L: -200...+900°C
Type T, J, K, S, B, N to DIN EN60584;
Type U, L to DIN 43710;with cable open circuit monitor
Integration time 200 ms
Output
(loop power
supply)
Output signal 24 V +/- 10%, 25 mA (internal limit, short circuit
protected)
Option: 100 mA, without short circuit protection
Number 1
Output (relays) Output signal Binary, switches on reaching the set point
Number 4
Contact type 1 potential free changeover contact
Contact loading <= 250 VAC, 3A / 30 VDC, 3A
Process display