5.3 Other operating parameters
Parameter Setting up selections
Default
settings
Actual
settings
User code
CODE
User presettable
operation code.
An already set code can only
be changed if the old code is
first entered and the unit
setting up released. Then a
new code can be set.
Values:
0000 to 9999
There is no operation
code active if “0" is set.
0
CO
DE
* Set point code
LICO
Set point change requires
a release code entry.
ON Set points are code
protected
OFF Set points can be
changed without setting
a code
OFF
LI
CO
This address is only active when an operation code is set up.
Switch on time delay
LOCK
After a power failure the
relay time delay switches
one after the other.
Value:
0.0 to 100.0 s
The time delay can be set in
0.4 second steps.
0,0
LO
CK
PA
RA
LIME
Parameter Setting up selections
Default
settings
Actual
settings
* Relay-
switch function
ALT
Changing the relay
function
OFF normal relay function
ON alternating relay function
see example chapter 6.1
Parameter only available when
MODE is on
MIN, MAX or TRD.
OFF
AL
T
* Time delay
DELY
Presettable time delay of
the relay after reaching
the set point. The delay is
settable in 0.4 second
steps.
Value:
0.0 to 100.0s
see example chapter 6.1
Parameter only available when
MODE is on
MIN, MAX or TRD.
0,0
DE
LY
End
END
End relay settings
Process display